FS4000/8 ~ Analogais ugunsdzēsības panelis 8 zonas

FS4000/8 ~ Analogais ugunsdzēsības panelis 8 zonas

Kods: 007965
Pieejams:
Cena: 114.41EUR

Sūtīt uz e-pastu

Ievadiet e-pastu:

Zonu skaits

8 ieejas zonas

Ieriču pieslēgšana (ugunsdzēsības detektori, trauksmes pogas, gāzes detektori)

Līdz 32 ierīcēm katrai zonai

Izejas

2 kontrolējamas izejas (19-27.5VDC/1A) / 2 trauksmes releja izejas 3A@125VAC ; 3A@30VDC / 1 releja izeja bojājumiem 3A@125VAC ; 3A@30VDC / 1 releja izeja bojājumiem 5VDC kad NO / 0VDC aktivācijas režīmā

Interfeiss

-

Vieta akumulātoram

2 x 7A @ 12Vdc

Barošanas avots

187 - 252 Vac

Model FS4000/8
Fire detection lines:
Maximum number of fire detectors in a line 32
 Type of the installation      two-wire
Maximum resistance of a line 100 Ω
Thresholds current values
Fault condition 0 – 6 mA
Duty mode 6 – 16 mA
Fire condition 16 – 80 mA
Short circuit: > 80 mA
Monitored fire alarm lines (EN54-2, type C)
Number 2 pcs
Type potential, relay with independent control
Electrical characteristics (19-27.5)V DC/1A
Common fire relay outputs
Number 2 pcs
Type potential-free,1 switching, 1 NO
Electrical characteristics 3А/125V AC, 3A/30V DC fire outputs and fire alarm outputs
Optional delay time for fire outputs activation 1,2,3,4,5,6 or 7 minutes
Evacuation condition available on access level 2
RS485 interface for network connection with Repeater panel optional interface on the FD4201
Dedicated status LED indicator for the RS485 interface it is applicable for Fire Alarm Routing Equipment (EN54-2, type E)
Indications of registered events
Light indication LED
Sound Built-in buzzer
Power supply
Voltage (187-252)V AC
lFrequency 50/60 Hz
Backup batteries
Battery type lead, gel electrolyte
Number of batteries 2 pcs
Nominal voltage of the backup battery 12V
Nominal capacity C20 (7,0) Ah
Charge voltage 28V DC
Operation in Duty mode upon interruption in main power supply:
Lines 24V / 1,2Ah 2 lines – 32 h 4 lines – 24 h 6 lines – 20 h 8 lines – 16 h
Common fault warning relay outputs
Number 1 pcs
Type potential-free, switching
Electrical characteristics 3А/125V AC, 3A/30V DC
Functional data
Functional data – Identification of manual call points – Zone dedicated label and Zone dedicated LED indication for fire, fault, disable – Detection for removed fire detector – Automatic reset of the fault warning condition – Logical “AND” scenario for fire detection lines – EN54-2 Disabled condition and Test condition per fire detection line and fire alarm line – Direct mode (skip delay) function for each fire detection line – Test-LED functionality – Built-in buzzer for fire and fault condition – one tonal, continuous, can be suppressed – Test mode for fire alarm lines – Input for remote Reset fires operation – 8 types optional scenarios for common
Lines 24V / 4,5Ah 2 lines – 120 h 4 lines – 98 h 6 lines – 80 h 8 lines – 68 h
Lines 24V / 7,0Ah 2 lines – 180 h 4 lines – 140 h 6 lines – 110 h 8 lines – 90 h
Consumption on backup batteries supply – Configuration of 2 lines: < 35 mA at 24V DC – Configuration of 4 lines: < 45 mA at 24V DC – Configuration of 6 lines: < 55 mA at 24V DC – Configuration of 8 lines: < 65 mA at 24V DC
Power supply to external devices
Voltage (19-27)V DC
Maximum current value (including current of contr.outputs) 1,2A
Fuses
Main supply 230V 4.0 A
Backup battery 6.0 A
Dimensions 304mm x 222mm x 94mm
Weight (backup batteries not included) 0.98 kg